A silent cooling tower is an evaporative unit designed and equipped to keep its sound emissions below the acoustic limits of its surroundings without losing cooling capacity. In civil buildings such as hotels, hospitals or offices, noise control can be just as decisive as the cooling demand itself.
In this project, Torraval Cooling supplied two open-circuit induced draft cooling towers from the PME series in their SUPERSILENT version for the air conditioning system of an urban hotel. With the acoustic treatment applied, the installation reaches 47.1 dB(A) at 15 metres.
The client
The client is a hotel located in the heart of Madrid’s urban area, surrounded by residential and commercial buildings.
The installation is part of its HVAC system, in which the cooling towers dissipate the condensation heat from the chillers.
The need
The hotel needed an evaporative cooling system capable of meeting its thermal demand during the months of peak load.
This came with an equally demanding condition: the system could not disturb the acoustic comfort of guests or neighbours. In urban settings, the noise emitted by rooftop equipment is subject to the acoustic quality objectives set by regulations. At national level in Spain, Royal Decree 1367/2007 implements Noise Act 37/2003 with regard to acoustic zoning, quality objectives and noise emissions (BOE), and municipal bylaws then set the specific limits that apply.
The challenge
The main challenge was to reduce noise without compromising the thermal performance of the tower. In an operating cooling tower, noise comes mainly from three sources:
- The fan, which is the dominant source in most units.
- The air inlet and outlet, through which the sound generated inside spreads to the outside.
- The falling water hitting the tower basin, which produces what is known as rain noise.
Each of these sources calls for a different measure, and none can be treated in isolation. That is why a low-noise cooling tower is not achieved with a single accessory, but by studying the specific installation, the acoustic limits and the characteristics of the surroundings.
We have already explained these sources in detail in our article on noise in cooling towers, and how the type of fan affects acoustic impact in noise in cooling tower fans.
The solution
Torraval Cooling selected two open-circuit induced draft cooling towers from the PME series, SUPERSILENT model, a very low-noise version.
In induced draft towers, the fan is located at the top discharge and draws air through the fill. The differences between this configuration and forced draft, including in terms of noise, are covered in our guide to induced draft and forced draft cooling towers.
Silencers on the air outlets
Each tower incorporates silencers on the air outlets, which attenuate the noise that the fan and the airflow transmit to the outside through the discharge area.
Additional silencer on the air discharge
An additional silencer was installed on the air discharge on top of the base configuration. This is the measure that makes it possible to reach the final level of 47.1 dB(A) at 15 metres.
TCS remote control system with frequency inverter and probe
The towers include the Torraval Control System (TCS), with a frequency inverter and probe. The system adjusts the fan speed according to the ambient temperature, so the unit runs at a lower speed whenever the thermal load allows it. This results in quieter operation and energy savings at partial load.
Fully removable wall
Each tower features a fully removable wall, a patented Torraval solution that provides easy access to the interior for inspection, cleaning and maintenance of the internal components.
Benefits for the client
The solution combines the performance of evaporative cooling with acoustic treatment adapted to a noise-sensitive urban environment:
- Sound level of 47.1 dB(A) at 15 metres, compatible with the hotel use and the residential use of the surrounding area.
- Modulated operation thanks to the TCS, which reduces fan speed, noise and consumption when demand is lower.
- Simplified maintenance thanks to the removable wall, a key aspect for complying with cleaning and disinfection programmes in public-use facilities.
- Two independent towers, which provide operational flexibility.
Why a silent cooling tower in air conditioning
In the HVAC sector, the low noise level of the units connected to the system is a starting requirement, not an extra. That is why, in civil buildings, hospitals, schools or theatres, equipment selection begins with the installation environment and its acoustic limits.
Torraval has been designing and manufacturing cooling towers for more than 55 years as part of the MITA group. This experience allows us to propose, from the outset, the cooling tower for a hotel or other civil building that offers the best balance between capacity, consumption and sound emissions. You can see other cases in our projects in the HVAC sector, such as the PME-E open-circuit cooling towers for RAI in Rome or the installation of cooling towers with chillers in HVAC air conditioning.
Conclusion
This project shows that a silent cooling tower can meet the air conditioning demand of an urban hotel while complying with demanding acoustic requirements. The key lies in studying each noise source and combining the right solutions for the specific environment.
If your air conditioning project has acoustic constraints, take a look at our cooling solutions for HVAC and tell us about its conditions. Our technical team will help you select the most suitable configuration.